Level control connection
Level measurement
The level can be measured using the following sensors:
- Float switch
- Electrode
- Connection is protected against reverse polarity!
The inputs act as a normally open contact (NO):
- Float switch open or electrode non-immersed: Pump on
- Float switch shut or electrode immersed: Pump off
Pump dry-running protection
The level for dry-running protection can also be monitored via the following sensors:
- Float switch
- Electrode
- Connection is protected against reverse polarity!
The input acts as a normally open contact (NO):
- Float switch open or electrode non-immersed: water level below min. level
- Float switch shut or electrode immersed: water level sufficient
The terminals are fitted with a converter bridge at the factory.
High water level
The high water level can also be monitored by the following sensors:
- Float switch
- Electrode
- Connection is protected against reverse polarity!
The input acts as a normally open contact (NO):
- Float switch open or electrode non-immersed: no high water
- Float switch shut or electrode immersed: High water alarm
Sensor connection
CAUTION
Property damage due to external voltage!
An external voltage which is applied destroys the component.
- Do not apply external voltage (connect potential-free).
Insert the connection cable laid by the customer through the threaded cable glands and secure it. Connect the wires to the terminal strip according to the connection diagram. For more information on the control modes and how they work, as well as the individual terminal numbers, please refer to the relevant description:
- Control modes for filling
- “Filling” control mode: 1x well, 1x pump, 1x float switch or electrode
- “Filling” control mode: 1x well, 1x pump, 2x float switches or electrodes
- “Filling” control mode: 1x well, 2x pumps, 2x float switches or electrodes
- “Filling” control mode: 1x well, 2x pumps, 3 float switches or electrodes
- “Filling” control mode: 1x well, 2x pumps, 4x float switches or electrodes
- “Filling” control mode: 2x wells, 2x pumps, 2x float switches or electrodes
- “Filling” control mode: 2x wells, 2x pumps, 4x float switches or electrodes
- Control modes for draining
- “Drain” control mode: 1x well, 1x pump, 1x float switch or electrode
- “Drain” control mode: 1x well, 1x pump, 2x float switches or electrodes
- “Drain” control mode: 1x well, 2x pumps, 2x float switches or electrodes
- “Drain” control mode: 1x well, 2x pumps, 3 float switches or electrodes
- “Drain” control mode: 1x well, 2x pumps, 4x float switches or electrodes
- “Drain” control mode: 2x wells, 2x pumps, 2x float switches or electrodes
- “Drain” control mode: 2x wells, 2x pumps, 4x float switches or electrodes
Use of electrodes
Electrodes can be connected in the following ways: