“Drain” control mode: 1x well, 1x pump, 1x float switch or electrode
ON/OFF | Switch-on and off level, switching cycle is determined by the cable length |
DR | Dry-running level |
When the fill level in the well rises and the switch on-level is reached, the pump switches on. The well is drained. When the switch off level is reached, the pump switches off after the set switch-off delay has elapsed. The switching cycle is defined by the cable length of the float switch.
To protect the pump from a dry run, install an additional float switch or electrode in the well:
- If the water level falls below the dry running level, the pump switches off. An error message appears on the display and an alarm sounds.
- If the dry-running level is exceeded, the alarm and error message are automatically reset.
1 | Current pump status | 4.1 | DR |
2 | Standby pump activated | 4.2 | ON/OFF |
3 | Control mode | ||
4 | Switching status of the float switch/electrode | ||
6 | Fieldbus active |
Overview of terminals
Function | DR | - | ON/OFF | - | - | - | - | - |
Terminal overview symbol | ||||||||
Float switch operating principle | ||||||||
Top contact | closed | − | closed | − | − | − | − | closed |
Bottom contact | Open | − | Open | − | − | − | − | Open |
Required menu settings
Menu and value to be set |
|