“Filling” control mode: 1x well, 2x pumps, 2x float switches or electrodes

HW

High water level

ON/OFF1

Switch-on/switch-off level 1

ON/OFF2

Switch-on/switch-off level 2

DR

Dry-running level

P1

Pump 1

P2

Pump 2

When the fill level in the tank drops and the first switch on-level (ON/OFF1) is reached, the first pump switches on. The tank is filled. When the water level in the tank continues to drop and the second switch on-level (ON/OFF2) is reached, the second pump switches on.

When the switch-off levels (ON/OFF2 and ON/OFF1) are reached, the pumps switch off after the set switch-off delay has elapsed. The switching cycle is defined by the cable length of the respective float switch. NOTICE! The base-load and peak-load pumps are cycled alternately (see menu 5.60).

To prevent the tank from overflowing, install a float switch or electrode in the tank:

  • If the high water level is exceeded, all pumps switch off. An error message appears on the display and an alarm sounds.
  • If the water level falls below the high water level, the alarm and error message are automatically reset.

To protect the pumps from a dry run, install an additional float switch or electrode in the well:

  • If the water level falls below the dry-running level, the pumps switch off. An error message appears on the display and an alarm sounds.
  • If the dry-running level is exceeded, the alarm and error message are automatically reset.
Application diagram
Application diagram

1

Current pump status

4.1

DR

2

Standby pump activated

4.2

ON/OFF2

3

Control mode

4.3

ON/OFF1

4

Switching status of the float switch/electrode

4.5

HW

6

Fieldbus active

Screen display
Screen display

Overview of terminals

Function

DR

-

ON/OFF1

-

-

ON/OFF2

-

HW

Terminal overview symbol

Float switch operating principle

Top contact

closed

closed

closed

closed

Bottom contact

Open

Open

Open

Open

Required menu settings

Menu and value to be set