“Filling” control mode: 2x wells, 2x pumps, 4x float switches or electrodes

HW

High water level

OFF1

Switch-off level 1

ON1

Switch-on level 1

OFF2

Switch-off level 2

ON2

Switch-on level 2

W1

Well 1

DR1

Dry-running level 1

P1

Pump 1

W2

Well 2

DR2

Dry-running level 2

P2

Pump 2

When the fill level in the tank drops and the first switch on-level (ON1) is reached, the first pump switches on. The tank is filled. When the water level in the tank continues to drop and the second switch on-level (ON2) is reached, the second pump switches on.

When the switch-off levels (OFF2 and OFF1) are reached, the respective pump switches off after the set switch-off delay has elapsed. NOTICE! The base-load and peak-load pumps are cycled alternately (see menu 5.60).

To prevent the tank from overflowing, install a float switch or electrode in the tank:

  • If the high water level is exceeded, all pumps switch off. An error message appears on the display and an alarm sounds.
  • If the water level falls below the high water level, the alarm and error message are automatically reset.

To protect the pumps from a dry run, install a float switch or electrode in each well:

  • If the water level falls below the dry running level, the corresponding pump switches off. An error message appears on the display and an alarm sounds.
  • If the dry-running level is exceeded, the alarm and error message are automatically reset.
Application diagram
Application diagram

1

Current pump status

4.1

DR1

2

Standby pump activated

4.2

ON1

3

Control mode

4.3

OFF1

4

Switching status of the float switches/electrodes for well 1

4.5

HW

5

Switching status of the float switches/electrodes for well 2

5.1

DR2

6

Fieldbus active

5.2

ON2

5.3

OFF2

Screen display
Screen display

Overview of terminals

Function

DR1

OFF1

ON1

DR2

OFF2

ON2

-

HW

Terminal overview symbol

Float switch operating principle

Top contact

closed

closed

closed

closed

closed

closed

closed

Bottom contact

Open

Open

Open

Open

Open

Open

Open

Required menu settings

Menu and value to be set