“Drain” control mode: 1x well, 2x pumps, 4x float switches or electrodes

ON1

Switch-on level 1

OFF1

Switch-off level 1

ON2

Switch-on level 2

OFF2

Switch-off level 2

DR

Dry-running level

P1

Pump 1

P2

Pump 2

When the fill level in the well rises and the first switch on-level (ON1) is reached, the first pump switches on. The well is drained. When the water level in the well continues to rise and the second switch on-level (ON2) is reached, the second pump switches on.

When the switch-off levels (OFF1 and OFF2) are reached, the respective pump switches off after the set switch-off delay has elapsed. NOTICE! The base-load and peak-load pumps are cycled alternately (see menu 5.60).

To protect the pumps from a dry run, install an additional float switch or electrode in the well:

  • If the water level falls below the dry-running level, the pumps switch off. An error message appears on the display and an alarm sounds.
  • If the dry-running level is exceeded, the alarm and error message are automatically reset.
Application diagram
Application diagram

1

Current pump status

4.1

DR

2

Standby pump activated

4.2

OFF1

3

Control mode

4.3

ON1

4

Switching status of the float switch/electrode

4.4

OFF2

6

Fieldbus active

4.5

ON2

Screen display
Screen display

Overview of terminals

Function

DR

OFF1

ON1

-

OFF2

ON2

-

-

Terminal overview symbol

Float switch operating principle

Top contact

closed

closed

closed

closed

closed

closed

Bottom contact

Open

Open

Open

Open

Open

Open

Required menu settings

Menu and value to be set