“Filling” control mode: 1x well, 2x pumps, 3 float switches or electrodes

HW

High water level

OFF

Switch-off level

ON1

Switch-on level 1

ON2

Switch-on level 2

DR

Dry-running level

P1

Pump 1

P2

Pump 2

When the fill level in the tank drops and the first switch on-level (ON1) is reached, the first pump switches on. The tank is filled. When the water level in the tank continues to drop and the second switch on-level (ON2) is reached, the second pump switches on.

When the switch-off level (OFF) is reached, all pumps switch off after the set switch-off delay has elapsed. NOTICE! The base-load and peak-load pumps are cycled alternately (see menu 5.60).

To prevent the tank from overflowing, install a float switch or electrode in the tank:

  • If the high water level is exceeded, all pumps switch off. An error message appears on the display and an alarm sounds.
  • If the water level falls below the high water level, the alarm and error message are automatically reset.

To protect the pumps from a dry run, install an additional float switch or electrode in the well:

  • If the water level falls below the dry-running level, the pumps switch off. An error message appears on the display and an alarm sounds.
  • If the dry-running level is exceeded, the alarm and error message are automatically reset.
Application diagram
Application diagram

1

Current pump status

4.1

DR

2

Standby pump activated

4.2

ON1

3

Control mode

4.3

ON2

4

Switching status of the float switch/electrode

4.4

OFF

6

Fieldbus active

4.5

HW

Screen display
Screen display

Overview of terminals

Function

DR

OFF

ON1

-

-

ON2

-

HW

Terminal overview symbol

Float switch operating principle

Top contact

closed

closed

closed

closed

closed

Bottom contact

Open

Open

Open

Open

Open

Required menu settings

Menu and value to be set