“Drain” control mode: 2x wells, 2x pumps, 4x float switches or electrodes

W1

Well 1

ON1

Switch-on level 1

OFF1

Switch-off level 1

DR1

Dry-running level 1

P1

Pump 1

W2

Well 2

ON2

Switch-on level 2

OFF2

Switch-off level 2

DR2

Dry-running level 2

P2

Pump 2

When the fill level in the well rises and the switch on-level (ON1 or ON2) is reached, the pump switches on. The corresponding wells are drained.

When the switch-off levels (OFF1 or OFF2) are reached, the respective pump switches off after the set switch-off delay has elapsed.

To protect the pumps from a dry run, install a float switch or electrode in each well:

  • If the water level falls below the dry running level, the corresponding pump switches off. An error message appears on the display and an alarm sounds.
  • If the dry-running level is exceeded, the alarm and error message are automatically reset.
Application diagram
Application diagram

1

Current pump status

4.1

DR1

2

Standby pump activated

4.2

OFF1

3

Control mode

4.3

ON1

4

Switching status of the float switches/electrodes for well 1

5.1

DR2

5

Switching status of the float switches/electrodes for well 2

5.2

OFF2

6

Fieldbus active

5.3

ON2

Screen display
Screen display

Overview of terminals

Function

DR1

OFF1

ON1

DR2

OFF2

ON2

-

-

Terminal overview symbol

Float switch operating principle

Top contact

closed

closed

closed

closed

closed

closed

closed

Bottom contact

Open

Open

Open

Open

Open

Open

Open

Required menu settings

Menu and value to be set