Possible error message during activation

Depending on the mains connection and the basic settings, the following error message may occur during activation. The error codes listed and their description apply to commissioning. A complete overview can be found in Chapter “Error codes”.

Code*

Fault

Software version

Cause

Remedies

E006

Rotating field error

all

  • Incorrect rotating field
  • Operation with single-phase AC current connection.
  • Establish a clockwise rotating field at the mains connection.
  • Deactivate rotating field monitoring (menu 5.68)!

E080.x

Pump fault

Up to 2.01.x

Operation with single-phase AC current connection.

Deactivate motor current monitoring (menu 5.69)!

E080.x

Pump fault

From 2.02.x

  • No pump connected.
  • Motor current monitoring not set.
  • Connect pump or deactivate minimum current monitoring (menu 5.69)!
  • Set the motor current monitoring to the pump’s rated current.

Key:
*“x” = represents the pump to which the fault shown applies!