Application and function of the digital control inputs DI1 and DI2

The pump can be controlled through external potential-free contacts at the digital inputs DI1 and DI2. The pump can be

See section “Adjustment - Manual operation” for a detailed description of the OFF, MAX, MIN and MANUAL functions

In the “Settings” menu , select

  1. “External interfaces”
  2. “Function control input DI1” or “Function control input DI2”.

Possible settings:

Function control input DI1 or DI2

Selection option

Function control input DI1 or DI2

Not used

The control input does not have a function.

External OFF

Contact open: Pump is switched off.

Contact closed: Pump is switched on.

External MAX

Contact open: Pump is running in the mode set on the pump.

Contact closed: Pump is running with maximum speed.

External MIN

Contact open: Pump is running in the mode set on the pump.

Contact closed: Pump is running with minimum speed.

External MANUAL 1)

Contact open: Pump is running in the mode set
on the pump or in mode requested via bus communication.

Contact closed: Pump is set to MANUAL.

External key lock 2)

Contact open: Key lock is deactivated.

Contact closed: Key lock is activated.

Heating/cooling switchover 3)

Contact open: “Heating” active.

Contact closed: “Cooling” active.

1) Function: see section “Adjustment - Manual operation”.

2) Function: see “Key lock On” section.

3) To guarantee the heating/cooling switchover function operates correctly at the digital input:

  1. go to “Settings” menu, “Set control mode”, “Setting assistant” and select the “Heating & cooling” application and
  2. go to “Settings” menu, “Set control mode”, “Heating/cooling switchover” and select the “Binary input” option as switchover criterion.

NOTICE

notice

During regular operation, it is preferable to switch the pump on or off via the DI1 or DI2 digital input with EXT. OFF rather than via the mains voltage!

NOTICE

notice

The 24 V DC power supply is only available when the analogue input AI1 or AI2 has been configured to a type of use and a signal type or when the digital input DI1 has been configured.