Adjustment - Manual operation
All control modes, which are selected via the setting assistant, can be overridden with the functions of manual operation OFF, MIN, MAX, MANUAL.
DANGER
The pump can start despite the “OFF” function
The “OFF” function is not a safety function and is no replacement for disconnecting the power supply for maintenance work. Functions such as pump kick can start up the pump despite the “OFF” function being set.
- Always disconnect the pump from the power supply before carrying out any work!
Manual operation functions can be selected in the menu “Settings”→ “Manual operation”
“Manual operation (OFF, MIN, MAX, MANUAL)”
Function | Description |
---|---|
Control mode | Pump works according to the set controls. |
OFF | Pump is switched off. Pump is not running. |
MIN | The pump is set to minimum power. |
MAX | The pump is set to maximum power. |
MANUAL | Pump is working according to set control, which is meant for the “MANUAL” function. |
The manual operation functions OFF, MAX, MIN, MANUAL correspond to the functions Ext. OFF, Ext. MAX, Ext. MIN and Ext. MANUAL in their effect.
Ext. OFF, Ext. MAX, Ext. MIN and Ext. MANUAL can be triggered via the digital inputs or via a bus system.
Priorities
Priority* | Function |
---|---|
1 | OFF, External OFF (binary input), External OFF (bus system) |
2 | MAX, External MAX (binary input), External MAX (bus system) |
3 | MIN, External MIN (binary input), External MIN (bus system) |
4 | MANUAL, External MANUAL (binary input) |
* Priority 1 = highest priority
NOTICE
The “MANUAL” function replaces all functions including those which are controlled via a bus system.
If a monitored bus communication fails, the control mode set via the “MANUAL” function is activated (Bus Command Timer).
Adjustable control modes for the MANUAL function:
Control mode |
---|
MANUAL – Differential pressure Δp-v |
MANUAL – Differential pressure Δp-c |
MANUAL – Volume flow Q-const |
MANUAL – Speed n-const |