Installing the rechargeable battery
DANGER
Risk of fatal injury due to electrical current!
There is a risk of fatal injury when performing work on the open switchgear! The components carry current!
- Have work carried out by a qualified electrician.
- Avoid contact with earthed metal parts (pipes, frames etc.).
NOTICE
Mains-independent alarm
The alarm sounds as soon as the rechargeable battery is inserted. The alarm can only be switched off by removing the rechargeable battery again or by connecting the power supply.
By inserting a rechargeable battery, a mains-independent alarm signal can be issued in the case of a power failure. An audible, constant tone is emitted as an alarm. Observe the following points:
- Rechargeable battery type: E-Block, 9 V, Ni-MH
- In order to ensure trouble-free operation, charge the rechargeable battery prior to insertion or charge it for 24 h in the switchgear.
- The capacity of the rechargeable battery will fall if the ambient temperature drops. The alarm running time is reduced.
- Power supply connected.
- Main switch in the “0/OFF” position!
- Insert the rechargeable battery into the designated holder, see “Overview of components”.
- Plug in the connection cable.
- Alarm sounds!
- Turn the main switch to the “1/ON” position.
- Alarm off!
- Rechargeable battery installed.