Terminal diagram overview

Wiring diagram EC-L1... and EC-L2...

Terminal

Function

Terminal

Function

2/3

Output: Individual run signal pump 1

31/32

Input: Float switch or electrode “pump 2 in”

4/5

Output: Individual fault signal pump 1

33/34

Input: “High water” float switch or electrode

8/9

Output: Individual fault signal pump 2

37/38

Input: Pump 1 thermal winding monitor

10/11

Output: Individual run signal pump 2

39/40

Input: Pump 2 thermal winding monitor

13/14/15

Output: Collective run signal

41/42

Output: Analogue output for displaying the actual level value

16/17/18

Output: Collective fault signal

45/46

Input: Level sensor 4 – 20 mA

19/20

Output: Power output

49/50

Input: Leakage detection pump 1

21/22

Input: Extern OFF

51/52

Input: Leakage detection pump 2

25/26

Input: “Dry-running protection” float switch or electrode

55/56

Input: “Dry-running protection” float switch (ex-mode)

27/28

Input: “All pumps off” float switch or electrode

57/58

Input: Thermal winding monitor pump 1 (ex-mode)

29/30

Input: Float switch or electrode “pump 1 in”

59/60

Input: Thermal winding monitor pump 2 (ex-mode)

Terminal diagram EC-L3...

Terminal

Function

Terminal

Function

1/2

Output: Power output

33/34

Input: “All pumps off” float switch

3/4

Output: Individual run signal pump 1

35/36

Input: “Pump 1 on” float switch

5/6

Output: Individual run signal pump 2

37/38

Input: “Pump 2 on” float switch

7/8

Output: Individual run signal pump 3

39/40

Input: “High water” float switch

11/12

Output: Individual fault signal pump 1

41/42

Input: Level sensor 4 – 20 mA

13/14

Output: Individual fault signal pump 2

47/48

Output: Analogue output for displaying the actual level value

15/16

Output: Individual fault signal pump 3

63/64

Input: Leakage detection pump 1

17/18/19

Output: Collective run signal

65/66

Input: Leakage detection pump 2

20/21/22

Output: Collective fault signal

67/68

Input: Leakage detection pump 3

23/24

Input: Pump 1 thermal winding monitor

75/76

Input: “Dry-running protection” float switch (ex-mode)

25/26

Input: Pump 2 thermal winding monitor

77/78

Input: Thermal winding monitor pump 1 (ex-mode)

27/28

Input: Pump 3 thermal winding monitor

79/80

Input: Thermal winding monitor pump 2 (ex-mode)

29/30

Input: Extern OFF

81/82

Input: Thermal winding monitor pump 3 (ex-mode)

31/32

Input: “Dry-running protection” float switch