Switchgear configuration: Switching on ex-mode
Adapted functions
Ex-mode adapts the following functions:
- Follow-up times
- All follow-up times are ignored and the pumps switched off immediately!
- Dry-running level (by level sensor or dynamic pressure bell)
- The following actions are only possible once the “All pumps off” fill level has been exceeded:
- Reactivation of the pumps
- Resetting the error message
- Alarm dry-running protection (via float switch)
- Alarm manual reset (anti-reactivation lock)!
- Alarm thermal motor monitoring
- Alarm manual reset (anti-reactivation lock)!
Activating ex-mode
- Press the operating button for 3 s.
- Menu 1.00 appears.
- Turn the operating button until menu 5 appears.
- Press the operating button.
- Menu 5.01 appears.
- Turn the operating button until menu 5.64 appears.
- Press the operating button.
- Change the value to “on”: Turn the operating button.
- Press the operating button.
- Ex-mode switched on.