System impedances

NOTICE

notice

Maximum switching frequency per hour

The connected motor determines the maximum switching frequency per hour. Note the technical data of the connected motor! The maximum switching frequency of the motor must not be exceeded.

NOTICE

notice
  1. Depending on the system impedance and the maximum connections/hour of the connected consumers, voltage fluctuations and/or drops may occur.
  2. When using shielded cables, attach the shielding to the earth rail on one side of the switchgear!
  3. Always have connection carried out by a qualified electrician!
  4. Observe the installation and operating instructions for the connected pumps and signal transmitters.

3~400 V, 2-pole, direct starting

Power in kW

System impedance in ohm

Connections/h

2.2

0.257

12

2.2

0.212

18

2.2

0.186

24

2.2

0.167

30

3.0

0.204

6

3.0

0.148

12

3.0

0.122

18

3.0

0.107

24

4.0

0.130

6

4.0

0.094

12

4.0

0.077

18