Start automatic mode
Automatic mode after initial configuration
- The switchgear is closed.
- Configuration complete.
- Direction of rotation correct.
- Motor current monitoring set correctly.
- Start Easy Actions menu: Turn the operating button 180°.
- Select the pump for automatic mode: Turn the operating button until the menu item is displayed:
- Pump 1: P1 Auto
- Pump 2: P2 Auto
- Pump 3: P3 Auto - Press the operating button.
- Automatic mode is set for the selected pump. Alternatively, setting can be performed in Menu 3.02 to 3.04.
- Automatic mode switched on.
Automatic mode after shutdown
- The switchgear is closed.
- Checked configuration.
- Parameter input enabled: Menu 7.01 shows on.
- Press the operating button for 3 s.
- Menu 1.00 appears.
- Turn the operating button until menu 3.00 appears
- Press the operating button.
- Menu 3.01 appears.
- Press the operating button.
- Change value to “on”.
- Press the operating button.
- Value saved, pump enabled.
- Automatic mode switched on.