Check the direction of rotation of the connected pumps

NOTICE

notice

Rotating field, power supply and pump connection

The rotating field is routed from the mains connection directly to the pump connection. Check the required rotating field of the pumps to be connected (clockwise or counter-clockwise)! Observe the installation and operating instructions of the pumps.

Perform a test run to check the direction of rotation of the pumps. CAUTION! Damage to property! Perform the test run under the prescribed operating conditions.

  1. The switchgear is closed.
  2. Configuration of menu 5 and menu 1 complete.
  3. All pumps are switched off in menu 3.02 to 3.04: Value is “off”.
  4. The pumps are enabled in menu 3.01: Value is “on”.
  1. Start Easy Actions menu: Turn the operating button 180°.
  2. Select the pump’s manual operation mode: turn the operating button until the menu item is displayed:
    - Pump 1: P1 Hand
    - Pump 2: P2 Hand
    - Pump 3: P3 Hand
  3. Start test run: Press the operating button. The pump runs until the operating button is released.
  4. Check direction of rotation.
  5. Incorrect direction of rotation: Exchange the two phases on the pump connection.
  1. Direction of rotation checked and corrected as necessary. The initial configuration is complete.