Forced switching of the pumps in case of dry run, min. water level or high water
Forced switching depends on the selected operating mode:
- High water level
- Operating mode “drain”: A forced switch-on* of all pumps always occurs, irrespective of the signal transmitter used.
- Operating mode “fill”: A forced switch-off of all pumps always occurs, irrespective of the signal transmitter used.
- Dry-running level
- Operating mode “drain”: A forced switch-off of all pumps always occurs, irrespective of the signal transmitter used.
- Operating mode “fill”: Realise dry-running protection via the “Extern OFF” input.
- Min. water level
- Operating mode “fill”: A forced switch-on* of all pumps always occurs, irrespective of the signal transmitter used.
The following preconditions must be fulfilled so that a forced switch-on can be performed:
- Pumps are enabled (menu 3.01 to 3.04).
- The “Extern OFF” input is not active.