Connecting an external alarm signal

CAUTION

Do not apply external voltage!

An external voltage which is applied destroys the component.

An external alarm signal (horn, flashing light, etc.) can be connected. The output is switched in parallel to the collective fault signal (SSM).

  • Alarm signal suitable for DC voltage.
  • Connection load: 24 V=, max. 4 VA
  • NOTICE! Observe the correct polarity when connecting!
  • Activate output in menu 5.67.

Insert the connection cables laid by the customer through the threaded cable glands and secure. Connect the wires to the terminal strip according to the connection diagram. Use the terminal number shown in the connection overview on the cover.

Connection overview symbol
Connection overview symbol