Individual run signal (EBM) connection

DANGER

danger

Risk of fatal injury due to an external electrical power supply!

The external electrical power supply is also present at the terminals when the main switch is switched off! There is a risk of fatal injury!

  1. Disconnect external power supply before any work!
  2. Electrical work must be carried out by a qualified electrician!
  3. Observe local regulations!

A run signal is output for each pump (EBM) via a separate output:

  • Contact type: potential-free NO contact
  • Contact load:
    • Minimum: 12 V=, 10 mA
    • Maximum: 250 V~, 1 A

Insert the connection cables laid by the customer through the threaded cable glands and secure. Connect the wires to the terminal strip according to the connection diagram. Use the terminal number shown in the connection overview on the cover. The number shown in location “x” on the symbol indicates which pump it refers to:

  • 1 = pump 1
  • 2 = pump 2
  • 3 = pump 3
Connection overview symbol
Connection overview symbol