Connection of a level actual value display

CAUTION

Do not apply external voltage!

An external voltage which is applied destroys the component.

The actual level value is exported via a separate output. A voltage of 0 ... 10 V= is provided for this at the output:

  • 0 V = level sensor value “0”
  • 10 V = level sensor upper limit
  • Example:
    • Level sensor measurement range: 0 ... 2.5 m
    • Display range: 0 ... 2.5 m
    • Setting: 1 V = 0.25 m

Insert the connection cables laid by the customer through the threaded cable glands and secure. Connect the wires to the terminal strip according to the connection diagram. Use the terminal number shown in the connection overview on the cover.
Activate the function in menu 5.07 to output the actual level value.

Connection overview symbol
Connection overview symbol