High water alarm connection with separate float switch

DANGER

danger

Risk of explosion due to incorrect connection!

If the connected signal transmitter is installed in an explosive atmosphere (Ex zone), there is a risk of explosion due to incorrect connection:

  1. Do not connect electrode in an explosive atmosphere (Ex zone)!
  2. Connect the float switch using an Ex cut-off relay!
  3. Connect level sensor via a Zener barrier!
  4. Observe the section on explosive atmospheres in the appendix.
  5. Connection must be carried out by a qualified electrician.

CAUTION

Do not apply external voltage!

An external voltage which is applied destroys the component.

The high-water level can also be monitored by the following signal transmitters:

  • Float switch
  • Electrode
    • Only Control EC-L1 ... and EC-L2 ...
    • Hardware version 2 or higher
    • Connection is protected against reverse polarity!

The input acts as a normally open contact (NO):

  • Float switch open/electrode not immersed: No high water alarm
  • Float switch closed/electrode immersed: High water alarm

NOTICE! A separate signal transmitter for the high water level is recommended as an additional system safety measure.

Insert the connection cables laid by the customer through the threaded cable glands and secure. Connect the wires to the terminal strip according to the connection diagram. Use the terminal number shown in the connection overview on the cover.