Adjust motor current monitoring

Set the permissible rated current after connecting the pump.

8

Potentiometer for motor current monitoring

Set the motor current on the respective potentiometer with a screwdriver:

  • At full load, set the rated current in accordance with the rating plate.
  • At partial load, set the rated current 5 % above the current measured at the duty point.

The motor current monitoring can be fine tuned during commissioning. The actual motor current can be displayed during commissioning:

  • Currently set rated current of the motor monitoring (menu 4.25 ... 4.27)
  • Currently measured operating current of the pump (menu 4.29 ... 4.31)
Adjust motor current monitoring
Adjust motor current monitoring