Adjust motor current monitoring
Set the permissible rated current after connecting the pump.
8 | Potentiometer for motor current monitoring |
Set the motor current on the respective potentiometer with a screwdriver:
- At full load, set the rated current in accordance with the rating plate.
- At partial load, set the rated current 5 % above the current measured at the duty point.
The motor current monitoring can be fine tuned during commissioning. The actual motor current can be displayed during commissioning:
- Currently set rated current of the motor monitoring (menu 4.25 ... 4.27)
- Currently measured operating current of the pump (menu 4.29 ... 4.31)