High water alarm
The level can be measured via the following signal transmitters:
- Level sensor
- Set the switching point in the menu.
- Dynamic pressure bell
- Only “IPS” version! Set the switching point in the menu.
- Separate float switch
- Separate electrode
- Only Control EC-L1 ... and EC-L2 ...
- Hardware version 2 or higher
The signal transmitters must be installed according to the system's installation plan. Please observe the following points:
- Float switch: Float switches must be able to move freely in the operating space (pump chamber, tank)!
- Dynamic pressure bell: Install a bubbling-through system to optimally vent the dynamic pressure bell.
What to do in the event of an alarm
- Operating mode “drain”: A forced switch-on of all pumps always takes place in the event of an alarm, irrespective of the selected signal transmitter!
- Operating mode “fill”: A forced switch-off of all pumps always takes place in the event of an alarm, irrespective of the selected signal transmitter!
The pumps must be activated for the forced switch-on:
- Menu 3.01: Pumps are enabled.
- Extern OFF: Function is inactive.