Menu 3: Enable pumps

To operate the system, the operating mode must be set for each pump and the pumps enabled:

  • Every pump is set to the “auto” operating mode as the factory setting.
  • Automatic mode starts after the pumps have been enabled in menu 3.01.

NOTICE! Required settings for the initial configuration.

During the initial configuration, a direction of rotation check must be performed on the pumps and the motor current monitoring set exactly. Use the following settings to perform the initial configuration:

  • Switch off the pumps: Set menu 3.02 to 3.04 to “off”.
  • Enable pumps: Set menu 3.01 to “on”.

Menu no.

3.02 … 3.04

Software version: All

Description

Pump 1 ... Pump 3 operating mode

Value range

off, Hand, Auto

Factory setting

Auto

Explanation

  • off = pump switched off
  • Hand = manual operation pump, as long as the button is pressed.
  • Auto = level-control-dependent automatic operation of the pump

NOTICE! Change the value to “off” for the initial configuration!

Menu 3.02
Menu 3.02

Menu no.

3.01

Software version: All

Description

Enable pumps

Value range

on, off

Factory setting

off

Explanation

  • off = pumps are locked and cannot be started.
  • NOTICE! Manual operation or forced switch-on are also not possible!
  • on = pumps are switched on/off, depending on the operating mode set
Menu 3.01
Menu 3.01