Menu 1: Values for switching on and off

Menu no.

1.09

Software version: All

Description

Base-load pump switch-off delay

Value range

0 … 60 s

Factory setting

0 s

Explanation

Time until the base-load pump is switched off after the fill levels are reached.

Menu 1.09
Menu 1.09

Menu no.

1.10

Software version: All

Description

Peak-load pump activation delay

Value range

0 … 30 s

Factory setting

3 s

Explanation

Time until the peak-load pump is switched on after the fill levels are reached.

Menu 1.10
Menu 1.10

Menu no.

1.11

Software version: All

Description

Peak-load pump switch-off delay

Value range

0 … 30 s

Factory setting

1 s

Explanation

Time until the peak-load pump is switched off after the fill levels are reached.

Menu 1.11
Menu 1.11

Menu no.

1.12

Software version: All

Description

Base-load pump On level

Value range

0.06 ... 12.5 m (NOTICE! The actual value range is dependent on the setting in menu 5.09.)

Factory setting

0.40 m

Explanation

“Drain” operating mode: Value must be 0.03 m higher than the “Base-load pump Off level” (menu 1.13).

“Fill” operating mode: Value must be 0.03 m lower than the “Base-load pump Off level” (menu 1.13).

NOTICE! The menu item is only visible if the value “Level” or “Bell” have been set in menu 5.07.

Menu 1.12
Menu 1.12

Menu no.

1.13

Software version: All

Description

Base-load pump Off level

Value range

0.06 ... 12.5 m (NOTICE! The actual value range is dependent on the setting in menu 5.09.)

Factory setting

0.23 m

Explanation

“Drain” operating mode: Value must be 0.03 m lower than the “Base-load pump On” level (menu 1.12).

“Fill” operating mode: Value must be 0.03 m higher than the “Base-load pump On level” (menu 1.12).

NOTICE! The menu item is only visible if the value “Level” or “Bell” have been set in menu 5.07.

Menu 1.13
Menu 1.13

Menu no.

1.14

Software version: All

Description

Level peak-load pump 1 on

Value range

0.06 ... 12.5 m (NOTICE! The actual value range is dependent on the setting in menu 5.09.)

Factory setting

0.42 m

Explanation

“Drain” operating mode: The value must be 0.03 m higher than the “Peak-load pump 1 On” level (menu 1.15). The switch-on level must be greater than/equal to the switch-on level of the base-load pump (menu 1.12).

“Fill” operating mode: The value must be 0.03 m lower than the “Peak-load pump 1 Off” level (menu 1.15). The switch-on level must be lower than/equal to the switch-on level of the base-load pump (menu 1.12).

NOTICE! The menu item is only visible if the value “Level” or “Bell” have been set in menu 5.07.

Menu 1.14
Menu 1.14

Menu no.

1.15

Software version: All

Description

Peak-load pump 1 Off level

Value range

0.06 ... 12.5 m (NOTICE! The actual value range is dependent on the setting in menu 5.09.)

Factory setting

0.25 m

Explanation

“Drain” operating mode: The value must be 0.03 m lower than the “Peak-load pump 1 On” level (menu 1.14). The switch-off level must be greater than/equal to the switch-on level of the base-load pump (menu 1.13).

“Fill” operating mode: The value must be 0.03 m higher than the “Peak-load pump 1 On” level (menu 1.14). The switch-off level must be lower than/equal to the switch-off level of the base-load pump (menu 1.13).

NOTICE! The menu item is only visible if the value “Level” or “Bell” have been set in menu 5.07.

Menu 1.15
Menu 1.15

Menu no.

1.16

Software version: All

Description

Peak-load pump 2 On level

Value range

0.06 ... 12.5 m (NOTICE! The actual value range is dependent on the setting in menu 5.09.)

Factory setting

0.42 m

Explanation

“Drain” operating mode: The value must be 0.03 m higher than the “Peak-load pump 2 Off” level (menu 1.17). The switch-on level must be greater than/equal to the switch-on level of the peak-load pump (menu 1.14).

“Fill” operating mode: The value must be 0.03 m lower than the “Peak-load pump 2 Off” level (menu 1.17). The switch-on level must be lower than/equal to the switch-on level of the peak-load pump (menu 1.14).

NOTICE! The menu item is only visible if the value “Level” or “Bell” have been set in menu 5.07.

Menu 1.16
Menu 1.16

Menu no.

1.17

Software version: All

Description

Peak-load pump 2 Off level

Value range

0.06 ... 12.5 m (NOTICE! The actual value range is dependent on the setting in menu 5.09.)

Factory setting

0.25 m

Explanation

“Drain” operating mode: The value must be 0.03 m lower than the “Peak-load pump 2 On” level (menu 1.16). The switch-off level must be greater than/equal to the switch-off level of the peak-load pump (menu 1.15).

“Fill” operating mode: The value must be 0.03 m higher than the “Peak-load pump 2 On” level (menu 1.16). The switch-off level must be lower than/equal to the switch-off level of the peak-load pump (menu 1.15).

NOTICE! The menu item is only visible if the value “Level” or “Bell” have been set in menu 5.07.

Menu 1.17
Menu 1.17