Menu 1: Values for switching on and off
Menu no. | 1.09 |
Software version: All | |
Description | Base-load pump switch-off delay |
Value range | 0 … 60 s |
Factory setting | 0 s |
Explanation | Time until the base-load pump is switched off after the fill levels are reached. |
Menu no. | 1.10 |
Software version: All | |
Description | Peak-load pump activation delay |
Value range | 0 … 30 s |
Factory setting | 3 s |
Explanation | Time until the peak-load pump is switched on after the fill levels are reached. |
Menu no. | 1.11 |
Software version: All | |
Description | Peak-load pump switch-off delay |
Value range | 0 … 30 s |
Factory setting | 1 s |
Explanation | Time until the peak-load pump is switched off after the fill levels are reached. |
Menu no. | 1.12 |
Software version: All | |
Description | Base-load pump On level |
Value range | 0.06 ... 12.5 m ( |
Factory setting | 0.40 m |
Explanation | “Drain” operating mode: Value must be 0.03 m higher than the “Base-load pump Off level” (menu 1.13). “Fill” operating mode: Value must be 0.03 m lower than the “Base-load pump Off level” (menu 1.13). |
Menu no. | 1.13 |
Software version: All | |
Description | Base-load pump Off level |
Value range | 0.06 ... 12.5 m ( |
Factory setting | 0.23 m |
Explanation | “Drain” operating mode: Value must be 0.03 m lower than the “Base-load pump On” level (menu 1.12). “Fill” operating mode: Value must be 0.03 m higher than the “Base-load pump On level” (menu 1.12). |
Menu no. | 1.14 |
Software version: All | |
Description | Level peak-load pump 1 on |
Value range | 0.06 ... 12.5 m ( |
Factory setting | 0.42 m |
Explanation | “Drain” operating mode: The value must be 0.03 m higher than the “Peak-load pump 1 On” level (menu 1.15). The switch-on level must be greater than/equal to the switch-on level of the base-load pump (menu 1.12). “Fill” operating mode: The value must be 0.03 m lower than the “Peak-load pump 1 Off” level (menu 1.15). The switch-on level must be lower than/equal to the switch-on level of the base-load pump (menu 1.12). |
Menu no. | 1.15 |
Software version: All | |
Description | Peak-load pump 1 Off level |
Value range | 0.06 ... 12.5 m ( |
Factory setting | 0.25 m |
Explanation | “Drain” operating mode: The value must be 0.03 m lower than the “Peak-load pump 1 On” level (menu 1.14). The switch-off level must be greater than/equal to the switch-on level of the base-load pump (menu 1.13). “Fill” operating mode: The value must be 0.03 m higher than the “Peak-load pump 1 On” level (menu 1.14). The switch-off level must be lower than/equal to the switch-off level of the base-load pump (menu 1.13). |
Menu no. | 1.16 |
Software version: All | |
Description | Peak-load pump 2 On level |
Value range | 0.06 ... 12.5 m ( |
Factory setting | 0.42 m |
Explanation | “Drain” operating mode: The value must be 0.03 m higher than the “Peak-load pump 2 Off” level (menu 1.17). The switch-on level must be greater than/equal to the switch-on level of the peak-load pump (menu 1.14). “Fill” operating mode: The value must be 0.03 m lower than the “Peak-load pump 2 Off” level (menu 1.17). The switch-on level must be lower than/equal to the switch-on level of the peak-load pump (menu 1.14). |
Menu no. | 1.17 |
Software version: All | |
Description | Peak-load pump 2 Off level |
Value range | 0.06 ... 12.5 m ( |
Factory setting | 0.25 m |
Explanation | “Drain” operating mode: The value must be 0.03 m lower than the “Peak-load pump 2 On” level (menu 1.16). The switch-off level must be greater than/equal to the switch-off level of the peak-load pump (menu 1.15). “Fill” operating mode: The value must be 0.03 m higher than the “Peak-load pump 2 On” level (menu 1.16). The switch-off level must be lower than/equal to the switch-off level of the peak-load pump (menu 1.15). |