Cleaning and disinfection
- The pump chamber is decommissioned.
- Remove the chamber cover.
- Activate the pumping station:
- Pumping station without a switchgear: Put the plug into the socket.
- Pumping station with a switchgear: Activate the switchgear at the main switch. Set the automatic mode.
- Open the shut-off valve in the discharge pipe.
- Flush the discharge pipe with the flush connection attached. Disconnect the flush connection.
- Flush the inside of the pump chamber with clean water from top to bottom through the chamber opening.
- Disinfect the pump chamber.
- Drain the pump chamber.
- Do more steps 5 to 7 until the pump chamber, pump and level control device are cleaned.
- Close the shut-off valve in the discharge pipe.
- Pump out the leftover fluid through emergency draining.
- Decommission the pumping station.
- Let the pumping station dry out.
- Fit the chamber cover.
- The pump chamber is cleaned and disinfected. Each component can now be removed.