Connection of FK 17.1 motor

Wire number

Wire marking

Description

Motor connection cable

1

20

Temperature monitoring of motor winding

2

21

3

U

Mains connection: L1, L2, L3, earth

4

V

5

W

Green/yellow (gn-ye)

PE

6

Blank

Moisture probe cable

DK

Leakage detection of sealing chamber

Mains connection

  • Follow the rating plate for the mains connection.
  • Make sure that the mains power supply has a clockwise-rotating field.
  • Follow the local regulations for earthing.

Temperature monitoring connection

  • Connect the bimetallic sensors to the switchgear or through an evaluation relay. Recommendation: relay “CM-MSS”.
  • Connection values: max. 250 V~, 2 A, cos φ = 1.
  • When the threshold value is reached: Switch off the motor.

Leakage detection connection − sealing chamber

  • Connect the moisture probe through an evaluation relay. Recommendation: relay “NIV 101/A”.
  • The threshold is 30 kOhm.
  • When the threshold value is reached: Activate an alarm or switch off the motor (recommended).
Connection diagram: FK 17.1, direct starting, bimetallic sensor
Connection diagram: FK 17.1, direct starting, bimetallic sensor

Wire number

Wire marking

Description

Motor connection cable

1

10

Temperature monitoring of motor winding

2

11

3

U

Mains connection: L1, L2, L3, earth

4

V

5

W

Green/yellow (gn-ye)

PE

6

Blank

Moisture probe cable

DK

Leakage detection of sealing chamber

Mains connection

  • Follow the rating plate for the mains connection.
  • Make sure that the mains power supply has a clockwise-rotating field.
  • Follow the local regulations for earthing.

Temperature monitoring connection

  • Connect the PTC sensors to the switchgear or through an evaluation relay. Recommendation: relay “CM-MSS”.
  • Connection values: nominal voltage: 7.5 V=, max. voltage 30 V=.
  • When the threshold value is reached: Switch off the motor.

Leakage detection connection − sealing chamber

  • Connect the moisture probe through an evaluation relay. Recommendation: relay “NIV 101/A”.
  • The threshold is 30 kOhm.
  • When the threshold value is reached: Activate an alarm or switch off the motor (recommended).
Connection diagram: FK 17.1, direct starting, PTC sensor, with 7-core H07RN-F connection cable
Connection diagram: FK 17.1, direct starting, PTC sensor, with 7-core H07RN-F connection cable

Wire number

Wire marking

Description

Motor connection cable

7

20

Temperature monitoring of motor winding

8

21

1

U1

Mains connection: L1, L2, L3, start of winding

3

V1

5

W1

4

U2

Mains connection: L1, L2, L3, end of winding

6

V2

2

W2

Green/yellow (gn-ye)

PE

Earth

9

Blank

Moisture probe cable

DK

Leakage detection of sealing chamber

Mains connection

  • Follow the rating plate for the mains connection.
  • Make sure that the mains power supply has a clockwise-rotating field.
  • Follow the local regulations for earthing.

Temperature monitoring connection

  • Connect the bimetallic sensors to the switchgear or through an evaluation relay. Recommendation: relay “CM-MSS”.
  • Connection values: max. 250 V~, 2 A, cos φ = 1.
  • When the threshold value is reached: Switch off the motor.

Leakage detection connection − sealing chamber

  • Connect the moisture probe through an evaluation relay. Recommendation: relay “NIV 101/A”.
  • The threshold is 30 kOhm.
  • When the threshold value is reached: Activate an alarm or switch off the motor (recommended).
Connection diagram: FK 17.1, star-delta activation, bimetallic sensor, with 10-core H07RN-F connection cable
Connection diagram: FK 17.1, star-delta activation, bimetallic sensor, with 10-core H07RN-F connection cable

Wire number

Wire marking

Description

Motor connection cable

7

10

Temperature monitoring of motor winding

8

11

1

U1

Mains connection: L1, L2, L3, start of winding

3

V1

5

W1

4

U2

Mains connection: L1, L2, L3, end of winding

6

V2

2

W2

Green/yellow (gn-ye)

PE

Earth

9

Blank

Moisture probe cable

DK

Leakage detection of sealing chamber

Mains connection

  • Follow the rating plate for the mains connection.
  • Make sure that the mains power supply has a clockwise-rotating field.
  • Follow the local regulations for earthing.

Temperature monitoring connection

  • Connect the PTC sensors to the switchgear or through an evaluation relay. Recommendation: relay “CM-MSS”.
  • Connection values: nominal voltage: 7.5 V=, max. voltage 30 V=.
  • When the threshold value is reached: Switch off the motor.

Leakage detection connection − sealing chamber

  • Connect the moisture probe through an evaluation relay. Recommendation: relay “NIV 101/A”.
  • The threshold is 30 kOhm.
  • When the threshold value is reached: Activate an alarm or switch off the motor (recommended).
Connection diagram: FK 17.1, star-delta activation, PTC sensor, with 10-core H07RN-F connection cable
Connection diagram: FK 17.1, star-delta activation, PTC sensor, with 10-core H07RN-F connection cable