Connection of P 13 motor

Wire number

Wire marking

Description

Motor connection cable

1

20

Temperature monitoring of motor winding

2

21

3

U

Mains connection: L1, L2, L3, earth

4

V

5

W

Green/yellow (gn-ye)

PE

6

DK

Leakage detection of motor compartment

Moisture probe cable

DK

Leakage detection of sealing chamber

Mains connection

  • Follow the rating plate for the mains connection.
  • Make sure that the mains power supply has a clockwise-rotating field.
  • Follow the local regulations for earthing.

Temperature monitoring connection

  • Connect the bimetallic sensors through an evaluation relay with an approval for explosive atmospheres. Recommendation: relay “CM-MSS”.
  • Connection values: max. 250 V~, 2 A, cos φ = 1.
  • When the threshold is reached: Switch off the motor with a manual reactivation lock (which can be reset by hand only). WARNING! An automatic restart is not permitted.

Leakage detection connection − motor compartment

  • Connect the moisture probe through an evaluation relay. Recommendation: relay “NIV 101/A”.
  • The threshold is 30 kOhm.
  • When the threshold is reached: Activate an alarm or switch off the motor (recommended).

Leakage detection connection − sealing chamber

  • Connect the moisture probe through an evaluation relay with an approval for explosive atmospheres and an intrinsically safe circuit. Recommendation: relay “XR-4...”.
  • The threshold is 30 kOhm.
  • When the threshold is reached: Activate an alarm or switch off the motor (recommended).
Connection diagram: P 13, direct starting, bimetallic sensor, with 7-core H07RN-F or TGSH connection cable
Connection diagram: P 13, direct starting, bimetallic sensor, with 7-core H07RN-F or TGSH connection cable

Wire number

Wire marking

Description

Motor connection cable

1

10

Temperature monitoring of motor winding

2

11

3

U

Mains connection: L1, L2, L3, earth

4

V

5

W

Green/yellow (gn-ye)

PE

6

DK

Leakage detection of motor compartment

Moisture probe cable

DK

Leakage detection of sealing chamber

Mains connection

  • Follow the rating plate for the mains connection.
  • Make sure that the mains power supply has a clockwise-rotating field.
  • Follow the local regulations for earthing.

Temperature monitoring connection

  • Connect the PTC sensors through an evaluation relay with an approval for explosive atmospheres. Recommendation: relay “CM-MSS”.
  • Connection values: nominal voltage: 7.5 V=, max. voltage 30 V=.
  • When the threshold is reached: Switch off the motor with a manual reactivation lock (which can be reset by hand only). WARNING! An automatic restart is not permitted.

Leakage detection connection − motor compartment

  • Connect the moisture probe through an evaluation relay. Recommendation: relay “NIV 101/A”.
  • The threshold is 30 kOhm.
  • When the threshold is reached: Activate an alarm or switch off the motor (recommended).

Leakage detection connection − sealing chamber

  • Connect the moisture probe through an evaluation relay with an approval for explosive atmospheres and an intrinsically safe circuit. Recommendation: relay “XR-4...”.
  • The threshold is 30 kOhm.
  • When the threshold is reached: Activate an alarm or switch off the motor (recommended).
Connection diagram: P 13, direct starting, PTC sensor, with 7-core H07RN-F or TGSH connection cable
Connection diagram: P 13, direct starting, PTC sensor, with 7-core H07RN-F or TGSH connection cable