Connection of P 13 motor
Wire number | Wire marking | Description |
Motor connection cable | ||
1 | 20 | Temperature monitoring of motor winding |
2 | 21 | |
3 | U | Mains connection: L1, L2, L3, earth |
4 | V | |
5 | W | |
Green/yellow (gn-ye) | PE | |
6 | DK | Leakage detection of motor compartment |
Moisture probe cable | ||
− | DK | Leakage detection of sealing chamber |
Mains connection
- Follow the rating plate for the mains connection.
- Make sure that the mains power supply has a clockwise-rotating field.
- Follow the local regulations for earthing.
Temperature monitoring connection
- Connect the bimetallic sensors through an evaluation relay with an approval for explosive atmospheres. Recommendation: relay “CM-MSS”.
- Connection values: max. 250 V~, 2 A, cos φ = 1.
- When the threshold is reached: Switch off the motor with a manual reactivation lock (which can be reset by hand only).
Leakage detection connection − motor compartment
- Connect the moisture probe through an evaluation relay. Recommendation: relay “NIV 101/A”.
- The threshold is 30 kOhm.
- When the threshold is reached: Activate an alarm or switch off the motor (recommended).
Leakage detection connection − sealing chamber
- Connect the moisture probe through an evaluation relay with an approval for explosive atmospheres and an intrinsically safe circuit. Recommendation: relay “XR-4...”.
- The threshold is 30 kOhm.
- When the threshold is reached: Activate an alarm or switch off the motor (recommended).
Wire number | Wire marking | Description |
Motor connection cable | ||
1 | 10 | Temperature monitoring of motor winding |
2 | 11 | |
3 | U | Mains connection: L1, L2, L3, earth |
4 | V | |
5 | W | |
Green/yellow (gn-ye) | PE | |
6 | DK | Leakage detection of motor compartment |
Moisture probe cable | ||
− | DK | Leakage detection of sealing chamber |
Mains connection
- Follow the rating plate for the mains connection.
- Make sure that the mains power supply has a clockwise-rotating field.
- Follow the local regulations for earthing.
Temperature monitoring connection
- Connect the PTC sensors through an evaluation relay with an approval for explosive atmospheres. Recommendation: relay “CM-MSS”.
- Connection values: nominal voltage: 7.5 V=, max. voltage 30 V=.
- When the threshold is reached: Switch off the motor with a manual reactivation lock (which can be reset by hand only).
Leakage detection connection − motor compartment
- Connect the moisture probe through an evaluation relay. Recommendation: relay “NIV 101/A”.
- The threshold is 30 kOhm.
- When the threshold is reached: Activate an alarm or switch off the motor (recommended).
Leakage detection connection − sealing chamber
- Connect the moisture probe through an evaluation relay with an approval for explosive atmospheres and an intrinsically safe circuit. Recommendation: relay “XR-4...”.
- The threshold is 30 kOhm.
- When the threshold is reached: Activate an alarm or switch off the motor (recommended).