Suggestions on the pump chamber
Connection cabinet
It is recommended to use a connection cabinet on the wall in the concrete pump chamber. Cable wiring between devices in the pump chamber and the control cabinet can be made through this connection cabinet for easy replacement and maintenance.
Minimum diameter of the pump chamber
The minimum diameter of the concrete pump chamber:
- 1500 mm for EMUport CORE 20.2
- 1600 mm for EMUport CORE 20.2 with Rexa SUPRA pumps
- 2000 mm for EMUport CORE 45.2 and 60.2
Ventilation and illumination
Suggestions on ventilation and illumination in the pump chamber:
- Ventilation:
- Minimum air change is seven times per hour.
- Illumination:
- Install the light sources on the side, not on the top of the pump chamber.
- Recommended colour temperature is 4000 ... 5000 Kelvins.