Cleaning the inlet pipe, collection tank and overflow channel
Examine the inlet and clean it if necessary. Clean the collection tank and the overflow channel in this sequence:
- Collection tank
- Overflow channel
- The water for the cleaning can be collected in the collection tank and disposed of with the next pumping procedure.
1 | Cover of the inspection opening |
2 | Clamp |
3 | Fixation of the clamp |
4 | Locking handle of the clamp |
An inspection opening is fitted to the front side of the collection tank. It is possible to clean the collection tank through this opening.
- Detach the fixation on the clamp.
- Open the clamp and remove the cover.
- Clean the collection tank with a water jet.
- Attach the cover again and fasten it with the clamp.
- Tighten the fixation of the clamp. Max. tightening torque: 15 Nm (11.1 ft·lb)
1 | Cover of the supply box/distributor |
2 | Screwed connection |
The cover on the supply box/distributor can be removed for the cleaning of the inlet pipe and overflow channel.
- Loosen the screwed connections on the cover of the distributor/supply box.
- Remove the cover.
- Clean the inlet with a water jet.
- Clean the supply box/distributor and the overflow channel with a water jet.
- Put the cover back on and screw the bolts back in. Max. tightening torque: 9 Nm (6.6 ft·lb)