Maintenance and repair
DANGER
Danger of death through electrical shock!
Incorrect behaviour during electrical work results in death by electric shock.
- Only a qualified electrician must do the electrical work.
- Obey local regulations.
DANGER
Explosion hazard through potentially explosive atmosphere in the collection tank!
There can be an explosive atmosphere in the collection tank. During maintenance work, there is a risk of explosion. Follow these points:
- A potentially explosive atmosphere, zone 2, applies in a 1 m radius around the ventilation pipe. Obey the factory regulations.
- During maintenance work, make sure that the air will change eight (8) times each hour in the operating space.
Maintenance and repair work can only be done by a qualified staff (e.g. customer service). Obey EN 12056‑4 for the maintenance intervals:
- ¼ year for commercial operations
- ½ year for multi-residential buildings
- One year for detached houses
After ¼ year
- Visual inspection of the inlet pipe, clean it if necessary.
After ½ year
- Examine the connections for impermeability.
- Clean the collection tank and overflow channel. If overflows occur regularly, then make sure to clean the overflow channel monthly.
After 1 year
- Clean the solids separation tanks and screens.
After 2 years
- Change the oil of the sewage pump. If using a pencil electrode for sealing chamber monitoring, change the oil in the sealing chamber according to the display.
Write all maintenance and repair work in a log. The log must be signed by the qualified staff and the operator.
Do a test run after the maintenance work.