Installing the lifting unit

1

Slinging point

2

Fastening grooves for floor anchoring

3

Pump support bracket

4

Screw

5

L-bracket

6

Anchor bolt

Install the lifting unit. Prevent the lifting unit from buoyancy and twisting. Anchor the lifting unit to the floor.

  1. Installation preparing work is done.
  2. Installation location is prepared as shown in the consulting documents.
  3. Applicable fixation materials are prepared.
  1. Put the lifting unit at the installation location and align it to the pipework. NOTICE! Lifting unit must be upright. CAUTION! Make sure not to lean against, push or step on the shut-off valves for the solids separation tank, otherwise they can break.
  2. For the lifting unit supplied with pump support brackets, loosen the screws on the upper L-brackets.
  3. Adjust the faces of the pump support brackets with the floor. Hand tighten the screws on the support brackets.
  4. Mark the drilling holes for the fastening grooves. Mark the drilling holes for the fastening points of the pump support brackets.
  5. Put the lifting unit aside.
  6. Drill the holes according to the fixation materials used and clean the holes.
  7. Put the lifting unit back.
  8. Anchor the lifting unit to the floor with the fixation materials. NOTICE! Follow the information on the fixation materials. NOTICE! Max. tightening torque: 30 Nm
  9. Attach the pump support brackets to the floor with the bounded anchors.
  10. Tighten all screws. NOTICE! Max. tightening torque: 60 Nm
  11. Lay the connection cable. Obey applicable regulations.
  1. The lifting unit is installed. Next step: Connecting the discharge pipe.
Installing the lifting unit
Installing the lifting unit