Switchgear
Necessary basic functions and connections of the switchgear
For safe operation of the sewage lifting unit, make sure that the switchgear has these functions and connections.
Functions
- Control of two pumps in alternating operations with forced switching.
- Single pump operation
During maintenance, the lifting unit can operate with only one pump. Make sure to designate the pump and operate it based on the given operating mode. - Configurable overload protection
- Direction-of-rotation monitoring
- Adjustable measurement range for different level sensors
- Main switch
- Manual control of pumps
The pumps can only be switched on if the “Pump ON” level in the collection tank is reached. - High water alarm
Make sure to give an alarm signal when the high water level is reached.
Connections
- For each pump:
- Power connection in direct or star-delta activation, depending on the pump
- Winding temperature monitoring using bimetallic strip or PTC sensor (FKT 20.2)
- Moisture probe for the motor compartment monitoring
- Moisture probe for sealing chamber monitoring
- Signal transmitter for the level control device
- Level sensor
- Intrinsically safe electric circuit (depending on local statutory regulations)