Switchgear
The switchgear is pre-wired and factory-set. Obey local regulations to lay all connection cables to the switchgear and mains connection.
The switchgear has these basic functions:
- Level-dependent control
- Motor protection
- Direction-of-rotation monitoring (only for the three-phase current)
- High water alarm
For detailed information, refer to the installation and operating instructions for the switchgear:
- Electrical connection of the lifting unit to the switchgear
- Overview and description of functions
- Setting of the switching points
Switching points
The switching points of the lifting unit can be adjusted to the inlet height of the lowest inlet. This results in a larger usable volume. The switching point data always refers to the floor.
Wilo-Control MS-L switchgear
For the Wilo-Control MS-L switchgear, set the switching points through fixed switch positions of DIP switch 3:
Switching points | Setting | Factory setting/selectable |
---|---|---|
Inlet height: 250 mm (10 in) | • | |
Inlet height: 315 mm (12.5 in) | o | |
Inlet height: 560 mm (22 in) | o |
Key
• = factory setting, o = adjustable
Wilo-Control EC-L switchgear
For the Wilo-Control EC-L switchgear, set the switching points through the values in the menus:
Switching points | Factory setting/selectable | Menu 5.09 | Menu 1.12 | Menu 1.13 | Menu 1.14 | Menu 1.15 | Menu 5.51 |
---|---|---|---|---|---|---|---|
Inlet height: 250 mm (10 in) | • | 1.00 | 0.50 | 0.11 | 0.53 | 0.16 | 0.55 |
Inlet height: 315 mm (12.5 in) | o | 1.00 | 0.63 | 0.11 | 0.64 | 0.16 | 0.66 |
Inlet height: 560 mm (22 in) | o | 1.00 | 0.94 | 0.11 | 0.96 | 0.16 | 0.97 |
Key
• = factory setting, o = adjustable, switching point unit: Metres (m)