Connecting the discharge pipe
1 | Lifting unit |
2 | Non-return valve |
3 | Double nipple |
4 | Shut-off valve |
5 | Hose nipple |
6 | Flexible collar |
7 | Pipe clamp |
8 | Y-piece |
9 | Discharge pipe |
Follow these points to connect the discharge pipe:
- Make sure that the discharge pipe is DN 32 or larger.
- Be conscious of the flow rate in the discharge pipe: 0.7 m/s (2.3 ft/s) to 2.3 m/s (7.5 ft/s).
- Do not decrease the pipe diameter.
- Make sure that all connections are fully tight.
- Install the discharge pipe as a “pipe loop” to prevent backflow from the primary public sewer.
- At the highest point, the bottom edge of the pipe loop must be above the locally given backflow level.
- To prevent frost, install the discharge line sufficiently deep.
- Install a shut-off valve.
- The lifting unit is installed correctly.
- The discharge pipe is installed correctly as shown in the consulting documents.
- Assembly materials are prepared:
1x Y-piece
2x shut-off valves
3x flexible collars
2x double nipples
5x hose nipples
6x pipe clamps
- Screw the double nipples in the non-return valves.Tightening torque: 8 Nm (5.9 ft·lb).
- To prevent leakage, it is recommended to apply seal connection with Teflon tape for all screw connections.
- Screw the shut-off valves on the double nipples.Tightening torque: 8 Nm (5.9 ft·lb).
- Screw a hose nipple in each shut-off valve. Tightening torque: 5 Nm (3.7 ft·lb)!
- Screw a hose nipple in each inlet port of the Y-piece. Tightening torque: 5 Nm (3.7 ft·lb).
- Slide a flexible collar over the hose nipple in each inlet port of the Y-piece.
- Slide the flexible collars over the hose nipples in the shut-off valves.
- Align the flexible collars centrally between the shut-off valves and the inlet ports of the Y-piece.
- Fasten the flexible collars to the hose nipples in the shut-off valves and inlet ports of the Y-piece with one pipe clamp at each side. Tightening torque: 5 Nm (3.7 ft·lb).
- Screw a hose nipple in the discharge port of the Y-piece. Tightening torque: 5 Nm (3.7 ft·lb).
- Slide a flexible collar over the discharge pipe.
- Slide the flexible collar over the hose nipple.
- To make sure that the discharge pipe is connected in a sound-isolated manner, keep a 40 … 60 mm (1.5 … 2.4 in) distance between the end of the discharge pipe and the end of the hose nipple.
- If the distance is too small, decrease the length of the discharge pipe.
- If the distance is too large, extend or replace the discharge pipe. - Align the flexible collar centrally between the discharge port of the Y-piece and the discharge pipe.
- Fasten the flexible collar to the hose nipple and the discharge pipe with one pipe clamp each. Tightening torque: 5 Nm (3.7 ft·lb).
- Discharge pipe is connected. Next step: Connecting the inlet.