Test run
Do a test run before operating the lifting unit in automatic mode. A test run examines the correct functioning and impermeability of the unit. If necessary, adjust the pump’s follow-up time to make sure of the optimum operation of the unit
- Lifting unit is installed correctly.
- Connections are checked for correctness.
- Activate the lifting unit: Put the plug into the socket.
- Set automatic mode on the switchgear.
- Open the shut-off valve in the discharge pipe.
- Unscrew the inspection cover on the collection tank.
- Slowly fill the collection tank with water through the inspection opening with a hose.
- Switch on and off the lifting unit through level control device.
- Do no less than two full pumping operations of all pumps for a test run.
- To examine the duty point, fill the discharge pipe fully with water. Do more test runs until the discharge pipe is fully filled.
- Screw the inspection cover on.
- Examine all connections for impermeability.
- If all connections are leak-proof, the lifting unit can run in automatic mode.
- Test run is completed.
- Lifting unit is commissioned: Keep shut-off valve open in the discharge pipe.
- Lifting unit is in standby mode: Close the shut-off valve in the discharge pipe.