Removal

DANGER

danger

Danger through harmful fluid!

In case of an accident, the collected sewage flows into the operating space. There is a risk of a bacterial infection. Follow these points:

  1. Wear protective equipment:
  2. One-way protective coverall
  3. Sealed safety glasses
  4. Respiratory mask
  5. Clean and disinfect all equipment (e.g., diaphragm hand pump, hoses) after use.
  6. Disinfect the lifting unit and operating space.
  7. Dispose of rinsing water to the sewer
  8. Obey local regulations to dispose of protective clothing and cleaning material.
  9. Obey the factory regulations.

DANGER

danger

Danger of death through electrical shock!

Incorrect behaviour during electrical work results in death by electric shock.

  1. Only a qualified electrician must do the electrical work.
  2. Obey local regulations.

DANGER

danger

Danger through alone working!

Working in chambers, narrow rooms, and in areas with a risk of falling can be dangerous. Do not work alone.

  1. Only do this work with a second person.

WARNING

warning

Risk of burns from hot surfaces!

During operation, the motor housing can get hot. There is a risk of skin burns if component is touched.

  1. Cool down the motor to ambient temperature after switching off.

WARNING

warning

Risk of injury from sharp edges and the macerator!

The pump has a macerator. The macerator blades are sharp. Furthermore, there can be sharp edges on the suction port. There is a high risk of cuts. Follow these points:

  1. Do not touch the macerator.
  2. Carry the pump only by the handle.
  3. Wear cut-resistant gloves.
  1. The lifting unit is decommissioned.
  2. Protective equipment put on.
  3. All shut-off valves are closed.
  1. Pump out the remaining fluid using the diaphragm hand pump.
  2. Remove the inlet connection: Pull the inlet pipe out of the inlet seal.
  3. Remove the discharge pipe connection: Remove the flexible collar and drain the discharge pipe. DANGER! Risk of health because of contact with sewage. The remaining sewage goes out of the discharge pipe. Collect sewage in applicable tanks and dispose of it into the sewer.
  4. Remove the ventilation connection: Pull the ventilation pipe out of the HT double socket.
  5. Remove the drain connection: Remove the suction line of the diaphragm hand pump from the drain connection. DANGER! Risk of health because of contact with sewage. The remaining sewage goes out of the collection tank through the drain connection. Collect sewage in applicable tanks and dispose of it into the sewer system.
  6. Loosen the floor anchoring.
  7. Pull the lifting unit carefully out of the pipework.
  1. The lifting unit is disassembled. Next step: Cleaning and disinfecting the lifting unit and the working area.