Fuse on mains side
Circuit breaker
- Make sure the type and switching characteristics of the circuit breakers are compatible with the rated current of the connected product.
- Obey local regulations.
Lifting unit | Max. rated current | Fuse protection (recommended characteristic: C) |
---|---|---|
Single-phase current | ||
DrainLift SANI-S...M... | 5.4 A | 10 A |
Three-phase current | ||
DrainLift SANI-S...T... | 1.9 A | 6 A |
Residual-current device (RCD)
- If persons can touch the device and conductive fluids, install a residual-current device (RCD).
- Obey the regulations of the local energy supplier for the residual-current device (RCD).