Filling and venting the hydraulics
WARNING
Risk of injury from a pressurised and hot water jet!
Do not unscrew the drain plug while the pump is running or starting. The fluid will shoot out of the filling and venting opening.
- Switch off the pump before filling and venting the hydraulics.
- Prevent the on-site control from unapproved start-up.
Before switching on the pump, make sure that the hydraulics is filled with water, and properly vented. Follow the steps below (Description).
Drain LPC 40
- The Drain LPC 40 does not have a non-return valve in the suction port. Make sure that a foot valve is fitted to the suction pipe. Without this foot valve, filling and venting of the hydraulics is not possible
- Unscrew the plug from the filling/venting opening.
- Slowly fill the hydraulics and the suction pipe with water up to the filling/venting opening.
- Screw the plug into the filling/venting opening.
Drain LPC 50/LPC 80
- Unscrew the plug from the filling/venting opening.
- Slowly fill the hydraulics with water up to the filling/venting opening.
- Screw the plug into the filling/venting opening.