System impedances

NOTICE

notice

Maximum switching frequency per hour

The connected motor determines the maximum switching frequency per hour.

  1. Note the technical data of the connected motor.
  2. Do not exceed the maximum switching frequency of the motor.

NOTICE

notice
  1. Depending on the system impedance and the maximum connections/hour of the connected consumers, voltage fluctuations and/or drops may occur.
  2. When using shielded cables, attach the shielding to the earth rail on one side of the control device.
  3. Always have connection carried out by a qualified electrician.
  4. Observe the installation and operating instructions for the connected pumps and signal transmitters.

3~400 V, 2-pole, direct starting

Power in kW

System impedance in ohms

Connections/h

0.37

2.629

6 … 30

0.55

1.573

6 … 30

0.75

0.950

6 … 18

0.75

0.944

24

0.75

0.850

30

1.1

0.628

6 … 12

1.1

0.582

18

1.1

0.508

24

1.1

0.458

30

1.5

0.515

6 … 12

1.5

0.431

18

1.5

0.377

24

1.5

0.339

30

2.2

0.321

6

2.2

0.257

12

2.2

0.212

18

2.2

0.186

24

2.2

0.167

30

3.0

0.204

6

3.0

0.148

12

3.0

0.122

18

3.0

0.107

24

4.0

0.130

6

4.0

0.094

12

4.0

0.077

18

5.5

0.115

6

5.5

0.083

12

5.5

0.069

18