“Constant pressure control p-c” control mode: 2x pumps, with pressure sensor

1

Activation point

2

1st deactivation point

3

2nd deactivation point

The pressure sensor detects the actual pressure value. The pumps are switched on and off depending on the set thresholds:

  • If the pressure in the system falls below the activation threshold, both pumps switch on.
  • When the first deactivation threshold is exceeded, the first pump switches off after the set switch-off delay has elapsed.
  • When the second deactivation threshold is exceeded, the second pump switches off after the set switch-off delay has elapsed.

To protect the pump from a dry run, install an additional float switch or electrode in the well:

  • If the water level falls below the dry running level, the pump switches off. An error message appears on the display and an alarm sounds.
  • If the dry-running level is exceeded, the alarm and error message are automatically reset.
Functional diagram
Functional diagram

1

Current pump status

2

Standby pump activated

3

Control mode

4

Current pressure in the tank

6

Fieldbus active

Screen display
Screen display

Overview of terminals

Function

DR

-

-

-

-

-

Pressure sensor

-

Terminal overview symbol

Float switch operating principle

Top contact

closed

-

Bottom contact

open

-

Required menu settings

Menu and value to be set

NOTICE! The values shown in menus 5.11 and 1.01 correspond to the factory setting. Enter the system-specific values here.