“Constant pressure control p-c” control mode: 1x pump, with pressure switch

1

Activation point

2

Deactivation point

NOTICE! If a pressure switch is used, only one pump can be controlled. The pressure switch used detects the actual pressure value and defines the activation and deactivation threshold:

  • If the pressure in the system falls below the activation threshold, the pump switches on.
  • If the deactivation threshold is exceeded, the pump switches off after the set switch-off delay has elapsed.

To protect the pump from a dry run, install an additional float switch or electrode in the well:

  • If the water level falls below the dry running level, the pump switches off. An error message appears on the display and an alarm sounds.
  • If the dry-running level is exceeded, the alarm and error message are automatically reset.
Functional diagram
Functional diagram

1

Current pump status

3

Control mode

4

Switching state of pressure switch

6

Fieldbus active

Screen display
Screen display

Overview of terminals

Function

DR

-

ON/OFF

-

-

-

-

-

Terminal overview symbol

Float switch operating principle

Top contact

closed

-

Bottom contact

open

-

Pressure switch operating principle

Contact closed

Pump off

Contact open

Pump on

Required menu settings

Menu and value to be set