ModBus: Parameter overview
Holding register | Name | Data type | Scaling and unit | Elements | Access* |
---|---|---|---|---|---|
40001 | Communication profile version | UINT16 | 0.001 |
| R |
40002 | Wink service | BOOL |
|
| RW |
40003 | Type of switchgear | ENUM |
| 8. EC | R |
40014 | BusCommandTimer | ENUM |
| 0. - | RW |
40015 | Drives on/off | BOOL |
|
| RW |
40025 | Control mode | ENUM |
| 0. p-c | R |
40026 | Actual value | INT16 | 0.1 bar |
| R |
40027 | Current setpoint | INT16 | 0.1 bar |
| R |
40041 | Pump mode 1 | ENUM |
| 0. Off | RW |
40042 | Pump mode 2 | ENUM |
| 0. Off | RW |
40062 | General status | BITMAP |
| 0: SBM | R |
40068 | Setpoint 1 | UINT16 | 0.1 bar |
| RW |
40074 | Application | ENUM |
| 2nd WP | R |
40139 - 40140 | Fault status | BITMAP32 |
| 0: Sensor fault | R |
40141 | Acknowledge | BOOL |
|
| R |
40142 | Alarm history index | UINT16 | 1 |
| RW |
40143 | Fault number alarm history | UINT16 | 0.1 |
| R |
40198 | Status of float switch | BITMAP |
| 0: Dry running | R |
Key
* R = read-only, RW = read- and write-accessible