Start automatic mode
Automatic mode after initial configuration
- The switchgear is closed.
- Configuration complete.
- Direction of rotation correct.
- Motor current monitoring set correctly.
- Start Easy Actions menu: Turn control knob 180°.
- Select the pump for automatic mode: Turn the control knob until the menu item is displayed:
– Pump 1: P1 Auto
– Pump 2: P2 Auto - Press the control knob.
- Automatic mode is set for the selected pump. Alternatively, setting can be performed in menu 3.02 to 3.03.
- Automatic mode switched on.
Automatic mode after shutdown
- The switchgear is closed.
- Checked configuration.
- Parameter input enabled: Menu 7.01 shows on.
- Press the control knob for 3 s.
- Menu 1.00 appears.
- Turn the control knob until menu 3.00 appears
- Press the control knob.
- Menu 3.01 appears.
- Press the control knob.
- Change value to “on”.
- Press the control knob.
- Value saved, pump enabled.
- Automatic mode switched on.