Check the direction of rotation of the connected pumps
NOTICE
Power supply and pump connection rotating field
The rotating field is routed from the mains connection directly to the pump connection.
- Check the required rotating field of the pumps to be connected (clockwise or counter-clockwise).
- Observe the installation and operating instructions of the pumps.
Perform a test run to check the direction of rotation of the pumps.
- The switchgear is closed.
- Configuration of menu 5 and menu 1 complete.
- All pumps are switched off in menu 3.02 to 3.03: Value is “off”.
- The pumps are enabled in menu 3.01: Value is “on”.
- Start Easy Actions menu: Turn control knob 180°.
- Select the pump’s manual operation mode: Turn the control knob until the menu item is displayed:
– Pump 1: P1 Hand
– Pump 2: P2 Hand - Start test run: Press the control knob. Pump runs for the set time (Menu 3.10) and then switches off again.
- Check direction of rotation.
- Incorrect direction of rotation: Exchange two phases on the pump connection.
- Direction of rotation checked and corrected as necessary. The initial configuration is complete.