Menu 3: Enable pumps

To operate the system, the operating mode must be set for each pump and the pumps enabled:

Required settings for the initial configuration

Carry out the following work during initial configuration:

Use the following settings to carry out this work:

Menu no.

3.00

Name

Operating settings

Description

Settings for the drives and mode of the pumps

Menu 3.00
Menu 3.00

Menu no.

3.01

Name

Enable pumps

Value range

on, off

Factory setting

off

Description

Deactivation or release of all pumps

Menu 3.01
Menu 3.01

Menu no.

3.02

Name

Operating mode, pump 1

Value range

off, Hand, Auto

Factory setting

Auto

Description

For the operating mode of pump 1, manual on (hand-operated), manual off (off) and automatic mode can be selected.

In manual operation, alarms such as dry run and thermal winding contact are still taken into account.

Menu 3.02
Menu 3.02

Menu no.

3.03

Name

Operating mode, pump 2

Value range

off, Hand, Auto

Factory setting

Auto

Description

In the operating mode of pump 2, you can choose between manual on (Hand), manual off (off) and automatic mode (Auto).

In manual mode, alarms such as dry run and or thermal motor monitoring are still taken into account.

Menu 3.03
Menu 3.03