Menu 3: Enable pumps
To operate the system, the operating mode must be set for each pump and the pumps enabled:
- Every pump is set to the “auto” operating mode as the factory setting.
- Automatic mode starts after the pumps have been enabled in Menu 3.01.
Required settings for the initial configuration
Carry out the following work during initial configuration:
- Check direction of rotation of the pumps
- Set precise motor current monitoring
Use the following settings to carry out this work:
- Switch off the pumps: Set menu 3.02 to 3.03 to “off”.
- Enable pumps: Set menu 3.01 to “on”.
Menu no. | 3.01 |
Name | Enable pumps |
Value range | on, off |
Factory setting | off |
Description | Deactivation or release of all pumps |
Menu no. | 3.02 |
Name | Operating mode, pump 1 |
Value range | off, Hand, Auto |
Factory setting | Auto |
Description | For the operating mode of pump 1, manual on (hand-operated), manual off (off) and automatic mode can be selected. In manual operation, alarms such as dry run and thermal winding contact are still taken into account. |
Menu no. | 3.03 |
Name | Operating mode, pump 2 |
Value range | off, Hand, Auto |
Factory setting | Auto |
Description | In the operating mode of pump 2, you can choose between manual on (Hand), manual off (off) and automatic mode (Auto). In manual mode, alarms such as dry run and or thermal motor monitoring are still taken into account. |