Menu 1: Values for switching on and off
Menu no. | 1.01 |
Name | Pressure setpoint |
Value range | 0.1 – 25.0 bar |
Factory setting | 4 bar |
Description | The pressure setpoint defines the pressure at the booster output. |
Menu no. | 1.04 |
Name | Pump start activation threshold |
Value range | 75 – 99% |
Factory setting | 95 % |
Description | Activation threshold of the pump in % of the pressure setpoint for starting the base-load pump or for pumps in general |
Menu no. | 1.07 |
Name | Deactivation threshold for base-load pump |
Value range | 101 – 125% |
Factory setting | 115 % |
Description | Deactivation threshold of the base-load pump in % of the pressure setpoint for stopping the base-load pump when only this is running. |
Menu no. | 1.08 |
Name | Deactivation threshold for peak-load pumps |
Value range | 101 – 125% |
Factory setting | 110 % |
Description | Deactivation threshold of the peak-load pumps in % of the pressure setpoint for stopping a peak-load pump when two or more pumps are running. |
Menu no. | 1.09 |
Name | Base-load pump deactivation delay |
Value range | 0 … 60 s |
Factory setting | 0 s |
Description | Delays the stop of the base-load pump when the stop threshold has been reached and the actual value remains permanently above the deactivation threshold. |
Menu no. | 1.10 |
Name | Peak-load pump activation delay |
Value range | 1 – 30 s |
Factory setting | 3 s |
Description | Delay for starting a peak-load pump when the start threshold has been reached and the current value remains permanently above the activation threshold. |