Menu 1: Values for switching on and off

Menu no.

1.00

Name

Setpoints

Description

Setting the control setpoints

Menu 1.00
Menu 1.00

Menu no.

1.01

Name

Pressure setpoint

Value range

0.1 – 25.0 bar

Factory setting

4 bar

Description

The pressure setpoint defines the pressure at the booster output.

Menu 1.01
Menu 1.01

Menu no.

1.04

Name

Pump start activation threshold

Value range

75 – 99%

Factory setting

95 %

Description

Activation threshold of the pump in % of the pressure setpoint for starting the base-load pump or for pumps in general

Menu 1.04
Menu 1.04

Menu no.

1.07

Name

Deactivation threshold for base-load pump

Value range

101 – 125%

Factory setting

115 %

Description

Deactivation threshold of the base-load pump in % of the pressure setpoint for stopping the base-load pump when only this is running.

Menu 1.07
Menu 1.07

Menu no.

1.08

Name

Deactivation threshold for peak-load pumps

Value range

101 – 125%

Factory setting

110 %

Description

Deactivation threshold of the peak-load pumps in % of the pressure setpoint for stopping a peak-load pump when two or more pumps are running.

Menu 1.08
Menu 1.08

Menu no.

1.09

Name

Base-load pump deactivation delay

Value range

0 … 60 s

Factory setting

0 s

Description

Delays the stop of the base-load pump when the stop threshold has been reached and the actual value remains permanently above the deactivation threshold.

Menu 1.09
Menu 1.09

Menu no.

1.10

Name

Peak-load pump activation delay

Value range

1 – 30 s

Factory setting

3 s

Description

Delay for starting a peak-load pump when the start threshold has been reached and the current value remains permanently above the activation threshold.

Menu 1.10
Menu 1.10

Menu no.

1.11

Name

Peak-load pump switch-off delay

Value range

0 … 30 s

Factory setting

1 s

Description

Delays the stop of a peak-load pump when the stop threshold has been reached and the actual value remains permanently above the deactivation threshold.

Menu 1.11
Menu 1.11