Overview of available parameters
The available parameters are shown in the following table.
Parameter (menu item) | Filling | Draining | Pressure switch | Pressure sensor |
---|---|---|---|---|
1.00 Values for switching on and off | ||||
1.01 Pressure setpoint | − | − | − | • |
1.04 Activation threshold of the pump in % of pressure setpoint | − | − | − | • |
1.07 Deactivation threshold of the base-load pump in % of pressure setpoint | − | − | − | • |
1.08 Peak-load pump deactivation threshold in % of pressure setpoint | − | − | − | • |
1.09 Deactivation delay base-load pump | • | • | • | • |
1.10 Activation delay peak-load pump | • | • | • | • |
1.11 Deactivation delay peak-load pump | • | • | • | • |
2.00 Fieldbus connection for ModBus RTU | ||||
2.01 ModBus RTU interface On/Off | • | • | • | • |
2.02 Baud rate | • | • | • | • |
2.03 User address | • | • | • | • |
2.04 Parity | • | • | • | • |
2.05 Stop bits | • | • | • | • |
3.00 Enable pumps | ||||
3.01 Enable pumps | • | • | • | • |
3.02 Pump 1 to Pump 2 operating mode | • | • | • | • |
3.10 Running time of pumps in manual operation | • | • | • | • |
4.00 Information | ||||
4.02 Current pressure value in bar | − | − | − | • |
4.05 Status of float switches | • | • | • | − |
4.12 Running time of switchgear | • | • | • | • |
4.13 Running time: Pump 1 | • | • | • | • |
4.14 Running time: Pump 2 | • | • | • | • |
4.17 Switching cycles switchgear | • | • | • | • |
4.18 Switching cycle: Pump 1 | • | • | • | • |
4.19 Switching cycle: Pump 2 | • | • | • | • |
4.22 Serial number of switchgear | • | • | • | • |
4.23 Switchgear type | • | • | • | • |
4.24 Software version | • | • | • | • |
4.25 Set value for the motor current monitoring: Pump 1 | • | • | • | • |
4.26 Set value for the motor current monitoring: Pump 2 | • | • | • | • |
4.29 Actual current in A for pump 1 | • | • | • | • |
4.30 Actual current in A for pump 2 | • | • | • | • |
5.00 Basic settings | ||||
5.01 Control mode | • | • | • | • |
5.02 Number of connected pumps | • | • | • | • |
5.03 Standby pump | • | • | • | • |
5.06 Signal acquisition pressure | − | − | • | • |
5.11 Pressure sensor measurement range | − | − | − | • |
5.39 Alarm signal with active “Extern OFF” input | • | − | − | − |
5.40 Switch “pump kick” function On/Off | • | • | • | • |
5.41 “Pump kick” permitted in “Extern OFF” | • | • | • | • |
5.42 “Pump kick interval” | • | • | • | • |
5.43 “Pump kick duration” | • | • | • | • |
5.44 Delay system | • | • | • | • |
5.45 Behaviour during sensor fault – number of pumps to be switched on | • | • | • | • |
5.57 Maximum running time for single-pump operation | • | • | • | • |
5.58 Collective run signal (SBM) function | • | • | • | • |
5.59 Collective fault signal (SSM) function | • | • | • | • |
5.60 Pump cycling | • | • | • | • |
5.62 Low water level (dry-running protection): Deactivation delay | • | • | • | • |
5.63 Low water level (dry-running protection): Reactivation time delay | • | • | • | • |
5.66 Acoustic alarm | • | • | • | • |
5.67 Output for an external signalling unit On/Off | • | • | • | • |
5.68 Mains connection rotating field monitoring On/Off | • | • | • | • |
5.69 Minimum motor current monitoring On/Off | • | • | • | • |
5.70 Max. switching frequency per hour, per pump | • | • | • | • |
5.71 Number of wells | • | • | − | − |
5.72 Number of float switches for pump levels | • | • | − | − |