Possible error message during activation

Depending on the mains connection and the basic settings, the following error message may occur during activation. The error codes listed and their description apply to commissioning. A complete overview can be found in Chapter “Error codes”.

Code*

Faults

Cause

Remedies

E006

Rotating field error

  • Incorrect rotating field
  • Operation with single-phase AC current connection.
  • Establish a clockwise rotating field at the mains connection.
  • Deactivate rotating field monitoring (menu 5.68)!

E080.x

Pump fault

  • No pump connected.
  • Motor current monitoring not set.
  • Connect pump or deactivate minimum current monitoring (menu 5.69)!
  • Set the motor current monitoring to the pump’s rated current.

Key:
* “x” = represents the pump to which the fault shown applies.