Connection of an actual pressure value display (pressure control only)

CAUTION

Property damage due to external voltage!

An external voltage which is applied destroys the component.

  1. Do not apply external voltage (connect potential-free).

The actual pressure value is transmitted via a separate output. A voltage of 0 to 10 V= is provided for this at the output:

  • 0 V = pressure sensor value “0”
  • 10 V = pressure sensor upper limit
  • Example:
    • Pressure sensor measurement range: 0 – 16 bar
    • Display range: 0 – 16 bar
    • Setting: 1 V = 1.6 bar

Insert the connection cable laid by the customer through the threaded cable glands and secure it. Connect the wires to the terminal strip according to the connection diagram. Use the terminal number shown in the connection overview on the cover.

Connection overview symbol